社旗Design and calculation of industrial coolers
社旗
:本文围绕工业冷却器的设计与计算展开,阐述了工业冷却器在工业生产中的关键作用,其能有效地降低设备或工艺流程的温度,保障系统稳定运行,详细介绍了设计环节,包括依据不同的工业场景和冷却需求确定冷却器的类型,如风冷式、水冷式等,同时考虑冷却介质的特性、流量等参数,在计算方面,着重讲解了热负荷的计算方法,通过分析被冷却对象的热量产生速率、环境温度等因素,精准计算出所需的换热量,还涉及冷却器传热面积、传热系数等关键参数的计算,以确保冷却器能达到预期的冷却效果。
1、Design basis
社旗Design Standard for Steel Structures GB50017-2017Steel Structure Design Manual, China Construction Industry Press, January 2004
Code for Construction and Acceptance of Steel Structures (GB50205-2020)
社旗
社旗British Code for Design of Steel Structures (BS5950)
社旗
2、Design load
社旗Load includes structural self weight, wind turbine constant load, live load, snow load, wind load, etc. The structural calculation adopts the ultimate stress method, therefore, the load value is larger than usual. The surface load is calculated based on the distribution coefficient and applied to the platform according to the line load. The wind load is calculated based on the wind vibration coefficient, body shape coefficient, and basic wind pressure to calculate the wind pressure values on four surfaces, which are then converted into line loads and applied to the columns. Auxiliary components such as stair handrails are applied to the stairs according to uniformly distributed loads.
社旗
1. Constant load
社旗
The self weight of the steel structure is automatically calculated by the program, and the node weight is considered based on the self weight of the structure multiplied by 1.3. The weight and fluid load of the radiator are applied by external forces.
社旗Platform constant load: 0.50kN/m2
社旗
社旗2. Live load
Live load of the platform for loading: 2.5kN/m2
3. Snow load
社旗
According to relevant design data, the snow pressure can be basically calculated as 0.4N/m2.
社旗
社旗4. Wind load
社旗
社旗Calculate according to the maximum value.
社旗
社旗Basic wind pressure: 0.35kN/m2, height variation coefficient of 1.8, wind vibration coefficient: 1.5, ground roughness category: Class A
社旗
Class.
Is the standard value of wind load, is the wind vibration coefficient at height Z, is the shape coefficient of wind load, and is the coefficient of wind pressure height variation.
社旗
社旗When the standard value of wind load is less than 0.75kpa, calculate based on 0.75 kPa and multiply by 1.4 times the safety factor. Namely
社旗5. Temperature load
社旗
社旗The temperature difference is relatively small. The structural form is single, and the linear expansion of steel has a relatively small impact on the overall performance of the structure, which can be ignored.
社旗
社旗6 Earthquake loads
社旗
社旗According to the seismic analysis design method: small earthquakes do not damage, medium earthquakes are repairable, and large earthquakes do not collapse. Small earthquake analysis can be divided into: bottom shear force method, response spectrum analysis, and elastic time history analysis. Medium earthquake analysis is calculated by multiplying small earthquake analysis by amplification factor.
社旗
社旗Seismic fortification intensity: 8 degrees
社旗Design basic seismic acceleration peak value: 0.3g
Construction site category: II site
社旗
Design grouping: Second group
Damping ratio: 0.05
This structure adopts MIADS software for overall modeling and analysis. During modeling, beam elements are mainly used for each structure. In order to facilitate loading, plate elements are established at the structural platform. Consolidation is used as the boundary condition at the bottom of each column, and constraints are applied at the connection between the column and the original structure according to the actual situation. The structure includes upright column, cross brace, slant support and upper and lower platform steel structure.
社旗
Load sub factors and load combinations:
Number | 社旗load 社旗 | 社旗Partial coefficient remarks | Partial coefficient remarks |
1 社旗 | dead load 社旗 | 1.3 | |
社旗2 社旗 | Dead load, when it has a restraining effect on uplift and overturning | 1.0 社旗 | |
3 社旗 | Dead load, when acting together with wind load and live load | 社旗1.2 社旗 | |
社旗4 社旗 | 社旗Live load | 1.6 | |
社旗5 社旗 | 社旗Live load, when combined with wind load 社旗 | 社旗1.2 | |
社旗6 社旗 | Wind load 社旗 | 1.4 社旗 | |
7 | 社旗When combined with wind load and live load 社旗 | 1.2 |
社旗3、 Radiator calculation
1. Material parameters
社旗Aluminum alloy adopts 6005-T1, with tensile strength and yield strength equivalent to 6063-T5, tensile strength ≥ 150Mpa, yield stress ≥ 110 Mpa. According to the performance table of aluminum alloy, it is found that 6063-T5 has a tensile strength of 185Mpa, yield stress of 145 Mpa, and fatigue strength of 90MPa.
社旗
社旗2. Working condition analysis
社旗The calculation of radiators can be divided into 1. lifting ondition,
3. operating condition (operating condition is divided into
4.support and lifting point participate in force simultaneously.
社旗
社旗5.support bears gravity, while lifting point bears horizontal force.
6.support does not bear any force, that is, when the overall structure is subjected to uneven settlement, there is a suspension at the bottom)
To ensure its stability, it is recommended that the foundation treatment should be pre compressed and settlement assessment should be carried out during the overall installation.
社旗
2.1 Hoisting conditions
社旗At this point, the radiator is only considered for its own weight due to the lack of fluid injection, and is lifted and installed through a side lifting point. Because no other accessories were installed during modeling, in order to estimate the weight more accurately, its self weight coefficient was defined as 1.3.
社旗
社旗The radiator structure consists of 1, frame 2, support beam 3, heat exchange tube 4, tube plate, and other ancillary structures. As the heat exchange tube and support beam are fixed together through a corrugated plate, it can be considered that the heat exchange tube participates in the structural stress, which leads to strain and stress generation.
社旗
社旗The overall structural model is
社旗
社旗Radiator structural model
社旗The overall deformation of the radiator during the lifting process
社旗
社旗Stress cloud diagram of radiator during lifting process
From its displacement cloud map, it can be seen that its overall deformation is 1.2mm, and the maximum stress is 15MPa
社旗
社旗
Stress cloud map of heat sink
社旗
社旗
社旗
社旗
社旗Displacement cloud map of heat sink
社旗From its displacement cloud map, it can be seen that its overall deformation is 1mm and the maximum stress is 2MPa. Through calculation, it can be seen that horizontal lifting has little effect on the heat dissipation fins, and its deformation and stress are far less than the standard requirements.
The vertical lifting situation is as follows:
社旗
社旗Vertical lifting stress cloud map
社旗
社旗
社旗



还没有评论,来说两句吧...